E09.012.246 Manual S-WG
41
9.1.3
C
ONTROL GENERAL
There is no need for a sensor in the tank, because when the pump starts to run, the inlet sensor of the water
heater is measuring the water temperature of the tank.
When there is no drawing water from the tank, the inlet sensor is measuring the water temperature in the
tank.
After ending a heat demand, the pump has a post turning time.
On the control panel, the tank or hot water temperature can be set.
When a remote wall controller is connected to the wire terminal (13) and (14), the setting of the tank tem-
perature can be done with this controller (Open Therm bus), also the night or weekend reduction of tank
temperature.
During a period of no tapping, the temperature inside the tank is maintained at the Setting temperature
automatically.
A safety control stops the water heater from firing, when the temperature difference between flow and return
gets higher than allowed at the actual load (flow monitoring, ΔT function).
Parameters: the default of the parameters of the water heater control have been set for this type of tanks.
9.1.4
C
ASCADE CONTROL
Up to twelve water heaters can be cascaded.
One water heater has to be appointed master, the other water heaters are appointed slaves, each with
his own address in the software.
The slaves are connected with two wires to the master.
Every individual water heater has a connection for a pump.
An external temperature sensor is placed at the inlet tube of the system (S3), sensing the temperature of
the inlet water of the water heaters: the sensor has to be placed
close to the connection of the tank
.
At a heat demand, the master water heater controls the heat output of the slaves, on base of the mea-
sured temperature of the external sensor.
When a slave stops burning, the pump connected to this slave has a post turning time.
When one water heater in the cascade installation is burning, the fans of the other water heaters are
turning at a low speed, preventing recirculation of the flue gases.
Flow monitoring cf. § 8.4 (page 37) remains active in every separate water heater of the cascade.
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......