E09.012.246 Manual S-WG
26
A: Twin pipe system with separate pipes for flue gas and air supply.
Example A
The total resistance is less than 200 Pa. This flue gas/air supply system is functional.
180
4
m
2m
2
m
2
m
2m
5
m
Water heater type:
S-WG 180
Flue gas
Diameter: 130 mm.
Number
Pa
Pa total
Straight tube m¹
total
9
6
54
Bend
90°
2
6
12
Flue outlet
conical
1
0.9
0.9
Total resistance flue gas outlet:
66.9
A
ir
su
pp
ly
Diameter: 130 mm.
Number
Pa
Pa total
Straight tube m¹
total
8
2
16
Bend
90°
2
2
4
Air inlet
H/D = 1.0
1
13.1
13.1
Total resistance air supply:
33.1
Total resistance flue gas outlet and air supply:
100 Pa