E09.012.246 Manual S-WG
8
TAKE NOTICE !
Between the water heater and the safety valve, DO NOT install an isolation valve or any other form of narrowing,
because this might disturb the correct functioning of the safety valve.
The correct safety valve has been supplied together with the S-WG water heater.
water heater
safety valves
Part number
S-WG 80
27112 Prescor B ¾ - 10 bar - 150 kW
E04.015.090
S-WG 100
27112 Prescor B ¾ - 10 bar - 150 kW
E04.015.090
S-WG 120
27112 Prescor B ¾ - 10 bar - 150 kW
E04.015.090
S-WG 150
27112 Prescor B ¾ - 10 bar - 150 kW
E04.015.090
S-WG 180
29007 Prescor B 1 - 10 bar - 250 kW
E04.015.091
The S-WG water heater and tank should be installed by a skilled installer according to all applicable standards
and regulations for tap water installations. Use the next scheme as guideline. When multiple water heaters and
tanks are applied, every combination has to be equipped with its own safety valve.