E09.012.246 Manual S-WG
55
9.6.2
T
WO
S-WG100
WATER HEATERS WITH TWO
450-
LITRES TANKS
Water heater connections, assigning codes:
For this system rule 2 must be applied.
Number the water heaters: water heater-1 is the water heater furthest from the tank(s), see picture.
Number de connection pipes directly connected to the water heaters: F1 en R1, see picture.
Number de horizontal connection pipes:
-
flow pipes starting at water heater-1: F1 t/m FF (here only an F1 and an FF), see picture.
-
return pipes starting at water heater-last (= water heater-2): R1 t/m RR (same remark), see picture.
Pipe sizes, water heater side:
From table
WH-100
, 2
nd
row:
-
All pipes F1 and R1 in the picture must measure at least 54
1,5 [mm
mm] (column F1/R1)
-
The pipes FF and RR must measure 67
1.9 [mm
mm] (column FF/RR).
Tank connections:
From table
T-100
, 2
nd
row: for 2 tanks A1 = B1 = 54
1.5 [mm
mm] is sufficient.
So for this system pipes sized at least 54
1.5 [mm
mm] are to be applied for all connections directly on water
heaters and tanks, and pipes sized at least 67
1.9 [mm
mm] for the flow and return connections between
them.
Equivalent length:
From table
EL
:
The maximum total length of flow and return pipes 67
1.9 [mm
mm] is 26.1 m.
So when 67
1.9 [mm
mm] is applied, the physical distance between water heaters and tanks may be half of
this, so ~ 13 m, at max. In case bends and/or valves are used, this distance becomes less than 13 m. Use the
table.
2 boilers
S-WG100
2 tanks
450 L
F1
R1
F1
R1
R1
FF
F1
RR
RR
1
2
FF
B1 A1
B1 A1
RR
FF
KOUD IN
1
2
Example 2
COLD IN
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......