E09.012.246 Manual S-WG
52
P2 = Grundfos UPS 32-100N
S-WG150
Number of tanks
Nr. of cascaded
water heaters
1 tank
2 tanks
3 tanks
4 tanks
5 tanks
6 tanks
7 tanks
8 tanks
1
P2
P2
P2
P2
P2
P2
P2
P2
2
x
x
P2
P2
P2
P2
P2
P2
3
x
x
x
P2
P2
P2
P2
P2
4
x
x
x
x
P2
P2
P2
P2
5
x
x
x
x
x
P2
P2
P2
6
x
x
x
x
x
x
x
P2
7
x
x
x
x
x
x
x
x
8
x
x
x
x
x
x
x
x
P3 = UPS 40-120 FB
S-WG180
Number of tanks
cascaded
units
1 tank
2 tanks
3 tanks
4 tanks
5 tanks
6 tanks
7 tanks
8 tanks
1
P3
P3
P3
P3
P3
P3
P3
P3
2
x
P3
P3
P3
P3
P3
P3
P3
3
x
x
P3
P3
P3
P3
P3
P3
4
x
x
x
P3
P3
P3
P3
P3
5
x
x
x
x
P3
P3
P3
P3
6
x
x
x
x
x
P3
P3
P3
7
x
x
x
x
x
x
P3
P3
8
x
x
x
x
x
x
x
P3
1
NB!
An x in the pump tables doesn’t necessarily mean that the corresponding installation cannot be built. If it
can, it will need specific design effort and pump choice. Please consult STREBEL for advice.
STREBEL part numbers
Water heater
Pump
Part nr.
S-WG 80
Pump Top-Z 25/10
E09.000.064
S-WG 100
Pump Top-Z 30/10
E09.000.065
S-WG 100/120/150
DHW pump UPS 32-100N
E09.000.112
S-WG 180
DHW pump UPS 40-120 FB
E09.000.115
9.5.2
N
OMINAL FLOW PER WATER HEATER TYPE
Water heater
Flow [m
3
/h]
S-WG 80
S-WG 100
S-WG 120
S-WG 150
S-WG 180
3.97
4.77
6.36
7.15
8.89
9.5.3
P
UMP CONTROL
The applied pump must be controlled by the S-WG water heater control. If, for any reason, an external
pump control is applied
without written approval of STREBEL
, then the complete warranty on the S-WG
water heater and all delivered parts will become invalid.
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......