E09.012.246 Manual S-WG
32
7
ELECTRICAL INSTALLATION
7.1
General
All the wiring is connected to a separate connector that is fitted in a socket. The connector can be taken from the
sockets without loosening the wiring. The connections are placed on top of the display panel and can be ac-
cessed by removing the water heater front door and the connector protection cover.
For operation the water heater needs a power supply of 230 Vac 50Hz.
The water heater connections are not life/neutral sensitive (the water heater is not phase-sensitive).
The wiring for the connections can be entered at the bottom of the water heater through the cable glands.
NOTICE: Before starting to work on the water heater, it must be switched off and the power supply to the
water heater must be disconnected.
Electrical wiring should be installed according to all applicable standards and regulations.
Working on the water heater should only be done by a skilled service engineer/installer and according to
all applicable standards and regulations.
7.2
Electrical connections
The following table describes the function of all connections of the water heater.
1-2
DO NOT USE
Do not connect any cable to these connections
3-4
TANK SENSOR
This external flow sensor measures the flow temperature at the system side. The sensor must be mounted
on the supply pipe at the system side, close to the tank. NOTICE: The sensor must be used when several
water heaters are cascaded with the internal cascade manager.
PARAMETER: No parameter settings needed.
5-6
DO NOT USE
Do not connect any cable to these connections
7-8
GENERAL BLOCKING
A heat demand that will start the burner will be blocked when terminals 7 and 8 are not bridged. This con-
nection is for the use of external safety devices (terminals must be bridged for allowing burner to fire).
9-10
EMPTY
Table is continued
DO NOT
USE
TANK
SENSOR
DO NOT
USE
GENERAL
BLOCKING
EMPTY
EXTERNAL
WPS
ON/OFF STAT
OR
OPEN THERM
0 -10
VDC
CASCADE
CONNECTION
LOCK-OUT
BURNER
BURNING
HEAT
DEMAND
CIRCULATION
PUMP P3
DO NOT USE
MAINS 230 VAC
CONNECTIONS
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......