E09.012.246 Manual S-WG
46
9.3.2
P
IPE CODES AT THE TANKS
’
SIDE
The codes of the piping in the picture are used in the installation tables in section 9.4 to determine the right in-
stallation diameters.
Numbering
Tank numbering may be useful to install flow and return connections in the right way, but doesn’t affect pipe
diameters. Only numbers of tanks and water heater type do (see tables § 9.4.2).
Encoding
Tank connections: A1 and B1 (entrance and exit). The values are found in the tank tables (§ 9.4.2)
Pipes between these connections: FF and RR, values from the water heater tables (§ 9.4.1).
For a given cascade, A1 equals B1.
9.3.3
E
QUIVALENT LENGTH
Piping between (cascaded) water heaters and one or more tanks. Equivalent length.
Piping connecting the water heater
s’ cascade with the tanks may not be too long, and moreover, every extra
component, such as bends and the like, contributes to the so-
called ‘equivalent length’, see table ‘Equivalent
lengths’ in § 9.4.3 on page 50.
ELABORATED EXAMPLES
At the end of this chapter, in § 9.5.4, three elaborated examples will be given demonstrating how to apply the
tables and values given in §§ 9.4 and 9.5.
FF
B1
A1
B1
A1
RR
FF
A1
B1
RR
RR
FF
A1
B1
FF
B1
A1
RR
B1 A1
RR
FF
FF
1
2
3
4
5
6
7
B1
RR
A1
FF
A1
B1
8
RR
FF
COLD IN
RR
FF
COLD WATER IN (SERVICE PIPE)
SUMMARY ENCODING PIPES WATER HEATER SIDE:
Assigning codes to a one water heater installation:
-
There’s only one flow pipe, encoded FF, and one return pipe, encoded RR. For the right diam-
eters see § 9.4.1, pick the table of the corresponding water heater type.
Assigning codes to cascades: two or more water heaters to connect:
-
First number the water heaters: water heater-
1 is the one that‘s situated the furthest away from
the tank(s).
-
Connections directly to the water heaters: F1 = R1 = 54
1,5 (mm
mm)
-
Number the horizontal flow pipes between water heaters: from F1 at water heater-1 to FF at
water heater-number-last.
-
Number the horizontal return pipes between water heater
s ‘reversely’: from R1 at water heater-
number-last to RR at water heater-1.
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......