E09.012.246 Manual S-WG
76
10.15 Setting the parameters with the display menu
The functions of the controller are embedded in de electronics. The values and settings that are being used for
these controlling functions can be changed by programming these values. This can be done by a skilled and
trained service engineer with the help of a computer, the correct software and an interface cable. The values and
settings that are used for these controlling functions are called parameters. A selection of these parameters can
be programmed on the unit itself, without the use of a computer. These settings can easily be done at the control
panel of the water heater.
The following table gives a list of these parameters that can be programmed by the display. All parameters that
are shown in the display, can be changed. NOTICE: Only the password for level 1 is issued in this manual.
When other “more advanced” parameters needs to be programmed, it can only be done by a skilled and trained
service engineer, who has access to level 2.
PASSWORD:
1342
PASSWORD:
MENU
SOFTW.
PARAM
DESCRIPTION
UNITS
TEXT DISPLAY
LEVEL 1
LEVEL 2
Display Modify
Display Modify
HE
AT
IN
G
A
1
P5BE
Step modulation (1=on 0=off)
-
S t
e p
m o d u
l
yes
no
yes
yes
2
P5AO
Blocking offset flow temperature control
°C
H E
s
O f f 1 3
yes
yes
yes
yes
3
P5AP
Proportional range temperature control
°C
H E
s
P r b 1 3
yes
no
yes
yes
4
P5AL
Hysteresis CH Flow temperature control
°C
H E
s c D i
f 1 3
yes
yes
yes
yes
5
P2IC
Integration time temperature control
s
H E
s
I n t 1 3
yes
no
yes
yes
6
P2MI
Blocking offset System CH temperature control
°C
H E
c O f f
3
yes
yes
yes
yes
7
P2MJ
Proportional range System CH temperature control
°C
H E
c P r b
3
yes
no
yes
yes
8
P2MK
Integration time CH temperature control
s
H E
c I n t
3
yes
no
yes
yes
9
P5AB
Timer Contact (1=on)
-
T i
m e r C o n t
yes
yes
yes
yes
DHW
B
1
P4AB
DHW Pump Config 0=Pump 1=TWV
-
D H
i
p m p /
t w v
yes
yes
yes
yes
2
P5CB
Flow temperature DHW tank low
°C
D H
i
f
l o w
L O
yes
yes
yes
yes
3
P5CK
Flow temperature DHW tank hi
°C
D H
i
f
l o w
H I
yes
yes
yes
yes
4
P5CL
Low Flow temperature time DHW
min
D H
i
L O t
i m e
yes
yes
yes
yes
5
P5CD
Legionella temperature
°C
L e
g i o
t e m p
yes
no
yes
yes
6
P5CI
Legionella hyst DHW tank temperature
°C
L e
g i o
h y s
t
yes
no
yes
yes
7
P5CJ
Legionella hold time (0=off)
min
L e
g i o
h o l
d
yes
no
yes
yes
8
P2KI
CH interrupt by Legionella (0=yes)(1=no)
-
L e
g i o
i n t
r
yes
no
yes
yes
9
P2LC
Regulation temperature offset DHWd
°C
D H d s c O f f 2
yes
yes
yes
yes
A
P2LE
Proportional range DHWd modulation
°C
D H d s c P r b 2 3
yes
no
yes
yes
B
P2LD
Regulation temperature hysteresis DHWd
°C
D H d s c D i
f 2
yes
yes
yes
yes
C
P2LF
integration time DHWd modulation
s
D H d s c I n t 2 3
yes
no
yes
yes
D
P2ML
Sys temp blocking offset DHW tank
°C
D H d s c O f f 3
yes
yes
yes
yes
E
P2MM
Sys temp blocking hysteresis DHW tank
°C
D H d s c D i
f 3
yes
yes
yes
yes
F
P5CA
Hysteresis DHW tank temperature
°C
D H
i
s c D i
f 4
yes
yes
yes
yes
G
P2KH
Gradient heat demand detect DHW tank temperature
°C
D H
i
d e t g r a d
yes
yes
yes
yes
CA
S
CA
DE
C
1
P2MA
Max number extra water heaters
-
M a
x C a s c U n
t
yes
no
yes
yes
2
P5DA
Bus address water heater
-
B u
s
a d r e s s
yes
no
yes
yes
3
P5DC
Dhw on entire cascade(0) only master(1)
-
D H
i
c a s / m a s
yes
no
yes
yes
4
P5DE
Extra Water heater output enable(1)
-
E x
t
r a
u n i
t
yes
yes
yes
yes
5
P5DF
Cascade detection (0=standalone 1=Leader)
-
C a
s
S i
/ M a
yes
no
yes
yes
6
P5BL
Power off total cascade (1)
-
P w
r O f f T o C a
yes
no
yes
yes
7
P5DB
Number of water heaters with common flue 0=None
-
C o m F l u N u m
yes
no
yes
yes
GE
NE
RA
L
D
1
P5BB
Analogue input Config (0=off 1=temp 2=power)
-
A n
I n p
C o n
yes
yes
yes
yes
2
P5AI
Minimum Temperature 0-10V input
°C
0
-
1 0 M i n T m p
yes
yes
yes
yes
3
P5BI
Altitude (in amounts of 100 ft.)
ft*100
A l
t
* 1 0 0 f
t
yes
yes
yes
yes
4
P2LK
Max cooling time
min
M a
x C o o l T i
m
yes
yes
yes
yes
5
P5BJ
Temperature display 1=on
-
T e m p O n D i
s p
yes
yes
yes
yes
6
P4AA
DHW 0=off 1=Indirect 2=Direct
-
D H W
1 = i 2 = d
yes
no
yes
yes
7
P4AD
pressure 0=off 1=sensor and 2=switch
-
c o n f
i g
yes
no
yes
yes
8
P4BD
Gas type values 0-2
-
g a
s t y p e
yes
no
yes
yes
9
P4BE
Soft start type values 0-2
-
c o n f
i g
yes
no
yes
yes
A
P5BN
Pump modes 0-4
-
c o n f
i g
yes
no
yes
yes
In the parameter table shown above one can see all the parameters that can be set on the unit without the use of
a laptop/computer.
In the following chapter “Controlling options and settings” the controlling options for hot water and cascading are
explained. In the explanation of these options there is a reference of all relevant parameters which are shown in
the table above and can be set on the unit.
IMPORTANT:
Do not change the parameters
P2LC, P2LD, P2ML, P2MM and P5BI
; they are present in the controller for diffe-
rent purposes than DHW control. Changing these parameters may affect water heater operation negatively
!
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......