E09.012.246 Manual S-WG
50
9.4.3
I
NTERCONNECTING PIPES
–
DIAMETERS AND EQUIVALENT LENGTH
When the water heaters and tanks are separated over some distance, the interconnecting pipes may only have a
certain maximum length, dependent of the number of bends and the like components. For every applied compo-
nent a so-
called ‘equivalent length’ is deducted from the total allowed.
The meaning of the connection
‘VL’ can be seen in the drawing below.
The diameter of this connection VL should meet at least the specified pipe diameter FF/RR. For this pipe con-
nection the maximum straight length
of flow and return part added *
has been specified in the table below.
*
The real available maximum distance VL between water heaters and tanks is therefore half of the
length specified in the table!
Drawing, explaining pipe connection ‘VL’:
Each component that
’s added to the straight pipes is contributing to the total resistance, and will therefore cause
a necessary reduction of straight length. The table contains a number of commonly used components and their
equivalent length:
Copper
pipe
diameter
Maximum
straight length
flow + return
equiv. length
90° elbow
R=0.5
D
equiv. length
90° elbow
R=1.0
D
equiv. length
45° bend
R=1.0
D
fully
ported
ball valve
RR/FF
m
m/elbow
m/elbow
m/bend
m/valve
54
1.5
24.2
2.8
1.0
0.6
0.4
67
1.9
26.1
3.3
1.1
0.7
0.5
80
2.1
28.5
3.8
1.3
0.8
0.6
93
2.3
31.9
4.6
1.6
0.9
0.7
106
2.5
36.7
5.7
2.0
1.1
0.9
133
2.8
44.3
7.5
2.6
1.5
1.1
159
3.0
58.2
10.8
3.8
2.2
1.6
table
EL
Example:
Suppose, for a project the diameter FF/RR has been specified the value 106
2.5, so the maximum allowed
straight length is 36.7 m (see table).
In the connection is added
- 4
bend 90°, R=0.5
D
- 2
fully ported ball valve
This gives a reduced allowed straight length of:
36.7
( 4
5.7 )
( 2
0.9 ) = 12.1 m
With this component configuration one may only use
12.1 m straight length
.
The distance between water heater main connections and tank main connections in this example is therefore
~6 m at max.
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......