E09.012.246 Manual S-WG
25
Flue gas and air supply resistance table
NOTICE: This table can only be used for a single flue/air system for one water heater. Do NOT use this table for
common flue/air systems with cascaded water heaters.
FLUE GAS PIPING
RESISTANCE [Pa]
Ø [mm] *
S-
WG80
S-
WG100
S-
WG120
S-
WG150
S-
WG180
straight tube/m
80
8.0
-
-
-
-
100
3.5
4.0
6.5
-
-
130
0.8
1.2
1.8
3.8
6.0
150
-
0.5
0.8
1.7
3.0
45° bend
80
4.0
-
-
-
-
100
1.7
2.0
3.2
-
-
130
0.4
0.6
0.8
1.9
3.0
150
-
0.2
0.4
0.8
1.5
90° bend
80
8.0
-
-
-
-
100
3.5
4.0
6.5
-
-
130
0.8
1.2
1.8
3.8
6.0
150
-
0.5
0.7
1.7
3
Flue outlet zeta=0.05
80
1.2
-
-
-
-
100
0.5
0.8
1.1
-
-
130
0.18
0.3
0.4
0.6
0.9
150
-
0.15
0.2
0.35
0.5
Flue outlet zeta=1.0
80
24
-
-
-
-
100
9.8
15.2
22.1
-
-
130
3.5
5.3
7.8
12
17.3
150
-
3.0
4.4
6.8
9.8
Flue outlet zeta=1.5
80
36
-
-
-
-
100
14.8
22.8
33.2
-
-
130
5.2
8.0
11.6
18
26
150
-
4.5
6.6
10.2
14.7
AIR SUPPLY PIPING
RESISTANCE [Pa]
Ø [mm] *
S-
WG80
S-
WG100
S-
WG120
S-
WG150
S-
WG180
straight tube/m
80
7.5
-
-
-
-
100
3.0
3.5
4.0
-
-
130
0.75
0.8
1.1
1.2
2.0
150
-
0.3
0.4
0.6
1.2
45° bend
80
3.5
-
-
-
-
100
1.5
1.7
2
-
-
130
0.4
0.4
0.5
0.6
1.0
150
-
0.15
0.2
0.3
0.6
90° bend
80
7.0
-
-
-
-
100
3.0
3.5
4.0
-
-
130
0.7
0.8
1.1
1.2
2.0
150
-
0.3
0.4
0.6
1.2
Air inlet zeta=1.0
80
18.1
-
-
-
-
100
7.4
11.4
16.7
-
-
130
2.6
4.0
5.8
9.1
13.1
150
-
2.3
3.3
5.1
7.4
CONCENTRIC PARTS
RESISTANCE [Pa]
Ø [mm] *
S-
WG80
S-
WG100
S-
WG120
S-
WG150
S-
WG180
roof terminal
80/125
61
-
-
-
-
100/150
-
39
45
69
86
130/200
-
-
-
15
23
outside wall terminal
80/125
22
-
-
-
-
100/150
-
19
24
40
48
straight tube/m
80/125
12
-
-
-
-
100/150
-
8.0
10
14
16
45° bend conc.
80/125
7
-
-
-
-
100/150
-
8.0
9.0
14
16
90° bend conc.
80/125
13
-
-
-
-
100/150
-
11
13
22
28
conc./par. adaptor
80/125
14
-
-
-
-
100/150
-
16
22
40
56
* Do not reduce pipe diameters relative to water heater connections
Roof
FLUE GAS OUTLET
AIR INLET
CONCENTRIC
Wall
H
D
H/D=1,0
zeta=1,0
AIR INLET
H
D
H/D=0,5
zeta=1,5
H
D
H/D=1,0
zeta=1,0
conical outlet
zeta=0,05
FLUE GAS OUTLET
open outlet
zeta=0
zeta = 0.0
open outlet
zeta = 0.05
conical outlet
H/D = 1.0
zeta = 1.0
H/D = 0.5
zeta = 1.5
H/D = 1.0
zeta = 1.0
Roof
Wall
FLUE GAS OUTLET
AIR INLET
CONCENTRIC
FLUE GAS OUTLET
AIR INLET
Summary of Contents for S-WG 100
Page 13: ...E09 012 246 Manual S WG 14 3 3 S WG tanks 300 Ltr 450 Ltr ...
Page 14: ...E09 012 246 Manual S WG 15 750 Ltr ...
Page 33: ...E09 012 246 Manual S WG 34 7 4 Electrical schematics ...
Page 34: ...E09 012 246 Manual S WG 35 ...
Page 122: ...E09 012 246 Manual S WG 123 notes ...
Page 123: ...E09 012 246 Manual S WG 124 notes ...
Page 124: ......