HRX-OM-S004
Chapter 8 Documents
8.1
Specifications
HRS Series
8-4
8.1.4
HRS100/150-W
∗
-40-
∗
Table 8-4 Specifications[HRS100/150-W
∗
-40-
∗
]
Model
HRS100-W
∗
-40-
∗
HRS150-W
∗
-40-
∗
Cooling method
Water-cooled refrigerated type
Refrigerant
R410A (HFC)
Control method
PIDcontrol
Ambient temperature
∗
1
o
C
2 to 45
Circulating fluid
∗
2
Tap water, Ethylene glycol aqueous solution 15%, Deionized water
Operating temperature range
∗
1
o
C
5 to 35
Cooling capacity 50/60Hz
∗
3
kW
10.0 / 11.0
14.5 / 16.5
Heating capacity
∗
4
kW
1.7 / 2.2
2.5 / 3.0
Temperature stability
∗
5
o
C
±1.0
Rated flow rate
50/60Hz (Outlet)
∗
6
L/min
42 / 56
Maximum flow rate
50/60Hz
L/min
55 / 68
Pump
capacity
Maximum lifting height
m 50
Minimum operating flow rate
50/60Hz
∗
7
L/min
28 / 42
Tank capacity
L
18
Circulating fluid outlet, circulating fluid
return port
Rc3/4 (Symbol F: G3/4, Symbol N: NPT3/4)
Pump drain port
Rc1/4 (Symbol F: G1/4, Symbol N: NPT1/4)
Supply side
press. range
MPa
0.2 to 0.5
Supply side
fluid temp.
o
C
5 to 35
Automatic fluid fill port
Rc1/2 (Symbol F: G1/2, Symbol N: NPT1/2)
Automatic
fluid fill
function
(Standard)
Over flow port
Rc1 (Symbol F: G1, Symbol N: NPT1)
Circulating
fluid
system
Wetted material
Stainless, Cupper(Heat exchanger brazing), Brass, Bronze
PTFE, PU, EPDM, PVC, NBR, PE, NR, PBT, POM, PP, Carbon, Ceramic
Temperature range
o
C
5 to 40
Pressure range
MPa
0.3 to 0.5
Required flow
50/60Hz
∗
5
L/min
33 / 34
38 / 40
Facility water pressure
differential
MPa
More than 0.3
Facility water inlet, outlet port
Rc3/4 (Symbol F: G3/4, Symbol N: NPT3/4)
Facility
water
system
Wetted material
Stainless, Cupper(Heat exchanger’s brazing ), Bronze, Brass
PTFE, NBR, EPDM
Power supply
AC380-415V 50/60Hz 3phase
Allowable voltage fluctuation ±10% (No continuous voltage fluctuation)
Rated
current
A 20
Earth leakage
breaker
(Standard)
Sensitivity mA
30
Rated operating current
50/60Hz
∗
5
A
6.4 / 7.2
7.7 / 9.5
Electric
system
Rated power consumption
50/60Hz
∗
5
kW (kVA)
3.4 / 4.4
(4.5 / 5.0)
4.5 / 6.0
(5.4 / 6.6)
Sound level (F
ront 1m / Height 1m)
∗
5
dB(A)
70
Water-proof specification
IPX4
Accessory
Alarm cord list label 2pc.(English 1pc./Japanese 1pc.),
Operation manual 2pc. (English 1pc./Japanese 1pc.),
Y strainer (40 mesh) 20 A 1pc., Barrel nipple 20 A 1pc. Drain pan for the pump 1pc.
Weight
(dry condition)
kg
151
154
EMC directive
2004/108/EC
Compliance
standard
CE Marking
Machinery directive
2006/42/EC
∗
1 Use 15% ethylene glycol aqueous solution if operating in a place where the circulating fluid temp. or ambient temperature is lower than
10
o
C. Please discharge the facility water from the facility water circuit when there is a risk of freezing.
∗
2 Use fluid in condition below as the circulating fluid.
Tap water: Standard of The Japan Refregeration And Air Conditioning Industry Association (JRA GL-02-1994)
15% ethylene glycol aqueous solution: diluted by tap water in condition above without any additives such as antiseptics.
Deionized water: Conductivity 1
μ
S/cm and higher (electrical resistivity 1M
Ω
・
cm and lower)
∗
3 (1)Facility water temp.: 32
o
C, (2)Circulating fluid : Tap water, (3)Circulating fluid temp.: 20
o
C, (4)Circulating fluid flow rate : Rated flow
rate, (5)Power supply: AC400V
∗
4 (1)Facility water temp.: 32
o
C, (2)Circulating fluid : Tap water, (3) Circulating fluid flow rate : Rated flow rate, (4)Power supply: AC400V
∗
5
(1) Facility water temp .: 32
o
C, (2)Circulating fluid : Tap water, (3)Circulating fluid temp.: 20
o
C, (4)Heat load : Same as the cooling
capacity, (5)Circulating fluid flow rate: Rated flow rate, (6)Power : AC400V, (7)External piping length: Minimum
∗
6
When circulating fluid outlet port pressure – return port pressure = 0.25MPa.
∗
7
Fluid flow rate to maintain the cooling capacity and to keep the circulating fluid discharge puressure to 0.5MPa or less. If the actual flow
rate is lower than this, please install a bypass piping.
Summary of Contents for HRS090-A
Page 8: ...HRX OM S004 Contents HRS Series...
Page 20: ...HRX OM S004 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS Series 2 6...
Page 56: ...HRX OM S004 Chapter 3 Transport and Setting Up 3 5 Circulating Fluid Supply HRS Series 3 36...
Page 164: ......
Page 174: ......
Page 192: ...HRX OM S004 Chapter 8 Documents 8 9 Daily Check Sheet HRS Series 8 18...
Page 195: ......