HRX-OM-S004
Chapter 5 Display and setting of various functions
HRS Series
5.9
Offset function
5-23
5.9.2
Usage example of offset function
Suppose that the circulating fluid discharge temperature of this
thermo-chiller is 30
o
C and the circulating fluid temperature that enters the
user's equipment is 29
o
C due to temperature drop while it is transferred to
the user's equipment in the piping:
■
When only the "set circulating fluid temperature" needs to be the same as the circulating
temperature supplied to the user's equipment:
Use "MODE 1" of the offset function, and set the offset temperature to "1.0"
o
C.
1. The thermo-chiller controls the circulating fluid temperature aiming at 31
o
C (set
circulating fluid temperature plus offset temperature).
2. The displayed circulating fluid temperature is the fluid temperature discharged from the
thermo-chiller (31
o
C).
Circulating fluid display
temperature
31
℃
Circulating fluid set
temperature
30
℃
Offset temperature
1
℃
This product
User’s equipment
Serial communication
Fluid discharge
temperature: 31
℃
30℃
Circulating fluid
temperature: 31
℃
Heat
dissipation
1
℃
Circulating fluid display
temperature
30
℃
Circulating fluid set
temperature
30
℃
This product
User’s equipment
Serial communication
Fluid discharge
temperature: 30
℃
Heat
dissipation
1
℃
29℃
Circulating fluid
temperature: 30
℃
Summary of Contents for HRS090-A
Page 8: ...HRX OM S004 Contents HRS Series...
Page 20: ...HRX OM S004 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS Series 2 6...
Page 56: ...HRX OM S004 Chapter 3 Transport and Setting Up 3 5 Circulating Fluid Supply HRS Series 3 36...
Page 164: ......
Page 174: ......
Page 192: ...HRX OM S004 Chapter 8 Documents 8 9 Daily Check Sheet HRS Series 8 18...
Page 195: ......