HRX-OM-S004
Chapter 3 Transport and Setting Up
HRS Series
3.2
Installation
3-5
z
Location that is subjected to static electricity, or conditions where static
electricity can discharge to the product.
z
Location that is subjected to strong high frequencies raditation
(microwaves).
z
Location that is subjected to potential lightening srtike.
z
Location where the product is affected by strong vibrations or impacts.
z
Condition that applies external force or weight causing the product to be
damaged.
z
Location without adequate space for maintenance as required.
z
Location that is exposed to splash of the water that is higher than IPX4.
z
Refer to the below for product installation or operation in an environment
temperature of 10
o
C or less.
z
Location at altitude of 3000m or higher (except during product storage and
transport). Refer to the below for details.
Thermo-chiller installation in high altitude of 1000 meters or more
Because of lower air density, the heat radiation efficiencies of the devices in the product will be
lower in the location at altitude of 1000m or higher. For this reason, the maximum ambient
temperature for the thermo-chiller operation and the cooling capacity will be reduced.
For product installation at a place of high altitude of 1000 meters or more, select a thermo-chiller
of the applicable capacity referring to the table below.
1. Max. ambient temp.: Use the product in lower ambient temperature than
the described value at each altitude.
2. Cooling capacity correction coefficient: Coefficient to calculate the
cooling capacity at each altitude
For the product operation at an altitude of 1800 meters,
“the cooling capacity at an altitude of 1800 meters” =
“the cooling capacity at an altitude of 1000 meter” x 0.8.
Installation/Operation in an ambient temperature of 10
o
C or less
Use ethylene glycol solution at a concentration of 15 % for the circulating
fluid.
Altitude [m]
1. Max. ambient
temp. [
o
C]
2. Cooling
capacity
correction
coefficient
Less than 1000m
45
1.00
1000 m or more - Less than
1500 m
42 0.85
1500m or more - Less than
2000m
38 0.80
2000m or more - Less than
2500m
35 0.75
2500m or more - Less than
3000m
32 0.70
Summary of Contents for HRS090-A
Page 8: ...HRX OM S004 Contents HRS Series...
Page 20: ...HRX OM S004 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS Series 2 6...
Page 56: ...HRX OM S004 Chapter 3 Transport and Setting Up 3 5 Circulating Fluid Supply HRS Series 3 36...
Page 164: ......
Page 174: ......
Page 192: ...HRX OM S004 Chapter 8 Documents 8 9 Daily Check Sheet HRS Series 8 18...
Page 195: ......