HRX-OM-S004
Chapter 5 Display and setting of various functions
5.20
Alarm customizing function
HRS Series
5-48
Table 5.20-3 Alarm setting and customizing (2/4)
①
Alarm operations
②
Alarm threshold and others
Code
Alarm name
Display
A.STP
A.R
U
N
P.RU
N
OFF Display
Default
setting
Settable
range
AL17
Refrigerant circuit
pressure (low
pressure side) drop
●
-
○
-
-
-
AL18
Compressor running
failure
●
-
○
-
-
-
Monitoring time
AL19
Communication error
●
●
-
○
----
(30)
∗
10
30
~
600
seconds
AL20
Memory error
-
○
-
-
-
-
-
AL21
DC line fuse cut
○
●
-
-
- -
AL22
Circulating fluid
discharge temp.
sensor failure
-
○
-
-
-
-
-
AL23
Circulating fluid return
temp. sensor failure
-
○
-
-
-
-
-
AL24
Compressor suction
temp. sensor failure
●
-
○
-
-
-
AL25
Circulating fluid
discharge pressure
sensor failure
○
●
-
●
- -
AL26
Compressor fluid
discharge pressure
sensor failure
●
-
○
-
-
-
AL27
Compressor suction
pressure sensor
failure
●
-
○
-
-
-
AL28 Pump
maintenance
-
●
-
○
- -
AL29
∗
11
Fan maintenance
-
●
-
○
- -
AL30
Compressor
maintenance
-
●
-
○
- -
AL31
Contact input 1 signal
detection
○
●
-
●
- -
AL32
Contact input 2 signal
detection
○
●
-
●
- -
AL37
Compressor
discharge temp.
sensor failure
●
-
○
-
-
-
AL38
Compressor
discharge temp. rise
●
-
○
-
-
-
*10: Default value when AS11 is set to either A.STP or A.RUN.
*11: Water-cooled type model does not generate this alarm.
Summary of Contents for HRS090-A
Page 8: ...HRX OM S004 Contents HRS Series...
Page 20: ...HRX OM S004 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS Series 2 6...
Page 56: ...HRX OM S004 Chapter 3 Transport and Setting Up 3 5 Circulating Fluid Supply HRS Series 3 36...
Page 164: ......
Page 174: ......
Page 192: ...HRX OM S004 Chapter 8 Documents 8 9 Daily Check Sheet HRS Series 8 18...
Page 195: ......