HRX-OM-S004
Chapter 5 Display and setting of various functions
HRS Series
5.8
Ready completion (TEMP READY) signal
5-21
5.
Select READY bandwidth with [
▲
] key or [
▼
] key, and enter by pressing the [SEL] key.
Table 5.8-3 Set value for READY mode
Set value
Explanation
Default
Sets READY bandwidth (range between the
upper and lower limit temperatures) for the set
circulating fluid temperature.
Centigrade
to
Fahrenheit
to
Setting of READY bandwidth (range between
the upper and lower limit temperatures) for
the set circulating fluid temperature.
Setting temperature unit for Centigrade: 0.1
o
C
Setting temperature unit for Fahrenheit: 0.1
o
F
Setting/checking: READY time
6.
Press the [SEL] key once.
Setting screen of READY time appears on the digital display.
PV
SV
7.
Set READY time with [
▲
] button or [
▼
] button, and enter with the [SEL] button.
Table 5.8-4 Set value
Set value
Explanation
Default
Setting and checking are not available when
READY mode setting is OFF.
to
Sets time that is to maintain the set circulating
fluid temperature before starting the product
operation.Setting unit: 1 second
8.
Press the [MENU] key once.
Returns to the main display (which shows the circulating fluid temperature).
PV
SV
Summary of Contents for HRS090-A
Page 8: ...HRX OM S004 Contents HRS Series...
Page 20: ...HRX OM S004 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS Series 2 6...
Page 56: ...HRX OM S004 Chapter 3 Transport and Setting Up 3 5 Circulating Fluid Supply HRS Series 3 36...
Page 164: ......
Page 174: ......
Page 192: ...HRX OM S004 Chapter 8 Documents 8 9 Daily Check Sheet HRS Series 8 18...
Page 195: ......