HRX-OM-S004
Chapter 5 Display and setting of various functions
HRS Series
5.20
Alarm customizing function
5-65
Setting/Checking: Operation setting when "Circulating fluid discharge pressure sensor error" alarm is generated
38.
Press the [SEL] key once.
Operation setting screen when "Circulating fluid discharge pressure sensor failure"
alarm is generated appears on the digital display.
PV
SV
39.
Set the product operation when "Circulating fluid discharge pressure sensor failure"
alarm is generated with [
▲
] key or [
▼
] key, and press [SEL] key to enter.
Table 5.20-27 Operation setting when the "Circulating fluid discharge pressure sensor failure" alarm is generated
Set value
Explanation
Initial value
(Default setting)
This alarm signal is not detected.
While this setting is ON, [ALARM] light on
the operation panel keeps blinking with the
light ON for 0.5 seconds and OFF for 3
seconds.
Operation continues when this alarm is
generated.
Operation stops when this alarm is generated.
✓
Setting/Checking: Operation setting when "Pump maintenance" alarm is generated
40.
Press the [SEL] key once.
Operation setting screen when "Pump maintenance" alarm is generated appears on the
digital display.
SV
41.
Set the product operation when "Pump maintenance" alarm is generated with [
▲
] key or
[
▼
] key, and press [SEL]key to enter.
Table 5.20-28 Operation setting when "Pump maintenance" alarm is generated
Set value
Explanation
Initial value
(Default setting)
This alarm is not detected.
✓
Operation continues when this alarm is
generated.
Summary of Contents for HRS090-A
Page 8: ...HRX OM S004 Contents HRS Series...
Page 20: ...HRX OM S004 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS Series 2 6...
Page 56: ...HRX OM S004 Chapter 3 Transport and Setting Up 3 5 Circulating Fluid Supply HRS Series 3 36...
Page 164: ......
Page 174: ......
Page 192: ...HRX OM S004 Chapter 8 Documents 8 9 Daily Check Sheet HRS Series 8 18...
Page 195: ......