HRX-OM-S004
Chapter 3 Transport and Setting Up
HRS Series
3.5
Circulating Fluid Supply
3-35
3.5.3
For option K “Fluid-fill port”
Open the cap of the fluid-fill port and supply the circulating fluid to the fluid level between
“HIGH” and “LOW” levels of the fluid level gauge. Close the cap after supplying.
Fig. 3-25 Filling the fluid to the fluid-fill port (An example)
z
Confirm that the fluid level is between “HIGH” and “LOW” levels of
the fluid level gauge. If it exceeds the specified level, the circulating
fluid will overflow.
z
Be sure to connect the piping from the overflow port to the drainage
pit to drain the excessive amount of the fluid from the tank.
z
Confirm that the valve of the drain port is closed to prevent the
supplied circulating fluid from draining out.