Chapter 3 Transport and Setting Up
HRS Series
3.4
Piping
3-27
z
Connect piping firmly. Incorrect piping might cause leakage of
supplied or drained fluid and wet surrounding area and facility.
z
Use caution not to allow dust and foreign matter to enter the water
circuit, etc. during connection of piping.
z
Securely connect the piping at the piping port with specific wrench
when tightening.
z
Incorrect piping can burst in service.
z
Use non-corrosive material for fluid contact parts of circulating
fluid and/or facility water. Using the materials that tend to rust or
corrode may cause clogging or/and leakages of the circulating
fluid and facility water circuits. In case of using these kinds of
materials, consider and carry out some prevention against the
rusting or corrosion by the customer side.
z
Do not generate a rapid change of pressure by water hammer, etc.
Internal parts of the product and/or the piping may be damaged.
z
Facility water temperature of the facility water outlet port might
rise up to approx.60deg.C.
3.4 Piping
Piping port size
Table 3-12 Piping port size
Name
Port size
∗
1
Recommended
tightening torque
Recommended piping
specification
Circulating fluid outlet port
Rc3/4
28 to 30N
・
m
1.0MPa and more
Circulating fluid return
port
Rc3/4
28 to 30N
・
m
1.0MPa and more
Facility water inlet port*1
Rc3/4
28 to 30N
・
m
Facility water outlet port*1
Rc3/4
28 to 30N
・
m
1.0MPa and more.
(Supply puressure : 0.3 to
0.5MPa)
Automatic fluid fill port
Rc1/2
20 to 25N
・
m
1.0MPa and more
(
Automatic fluid -fill pressure :
0.2 to 0.5MPa
)
Overflow port
Rc1
36 to 38N
・
m
ID25mm and more
Length 5m and less
Pump drain port
Rc1/4
8 to 12N
・
m
---
∗
1 : Water cooled type only.
[Tips]
<For HRS
∗∗∗
-AN-
∗
and
HRS
∗∗∗
-WN-
∗
>
A set of thread adapters that converts the connections from Rc to NPT is
enclosed as an accessory. For NPT thread, be sure to use this adapter.
<For HRS
∗∗∗
-AF-
∗
and HRS
∗∗∗
-WF-
∗
>
A set of thread adapters that converts the connections from Rc to G is
enclosed as an accessory. For G thread, be sure to use this adapter.
Summary of Contents for HRS090-A
Page 8: ...HRX OM S004 Contents HRS Series...
Page 20: ...HRX OM S004 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS Series 2 6...
Page 56: ...HRX OM S004 Chapter 3 Transport and Setting Up 3 5 Circulating Fluid Supply HRS Series 3 36...
Page 164: ......
Page 174: ......
Page 192: ...HRX OM S004 Chapter 8 Documents 8 9 Daily Check Sheet HRS Series 8 18...
Page 195: ......