HRX-OM-S004
Chapter 5 Display and setting of various functions
HRS Series
5.21
Communication function
5-73
14.
S Set slave addresses (simple communication protocol) with [
▲
] key or [
▼
] key, and
press [SEL] key to enter.
Table 5.21-8 Setting of slave addresses
Set value
Explanation
Initial value
(Default setting)
Setting/checking is possible only when the
serial protocol setting is simple
communication protocol.
to
Setting of slave addresses for simple
communication protocol
Setting range: 1 to 99
Setting/Checking: Communication speed (simple communication protocol)
15.
Press the [SEL] key once.
Setting screen of communication speed (simple communication protocol) is displayed
on the digital display.
PV
SV
16.
Set communication speed (serial communication protocol) with [
▲
] key or [
▼
] key, and
press [SEL] key to enter.
Table 5.21-9 Communication speed setting
Set value
Explanation
Initial value
(Default setting)
Setting/checking is possible only when the
serial protocol setting is simple
communication protocol.
1200bps
2400bps
4800bps
9600bps
✓
19200bps
Setting/Checking: BCC (simple communication protocol)
17.
Press the [SEL] key once.
Setting screen of BCC (simple communication protocol) is displayed on the digital
display.
PV
SV
Summary of Contents for HRS090-A
Page 8: ...HRX OM S004 Contents HRS Series...
Page 20: ...HRX OM S004 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS Series 2 6...
Page 56: ...HRX OM S004 Chapter 3 Transport and Setting Up 3 5 Circulating Fluid Supply HRS Series 3 36...
Page 164: ......
Page 174: ......
Page 192: ...HRX OM S004 Chapter 8 Documents 8 9 Daily Check Sheet HRS Series 8 18...
Page 195: ......