HRX-OM-S004
Chapter 5 Display and setting of various functions
HRS Series
5.21
Communication function
5-79
38.
Perform setting of the contact input signal 2 with [
▲
] key or [
▼
] key, and press [SEL]
key to enter.
Table 5.21-20 Setting of the contact input signal 2
Set value
Explanation
Initial value
(Default setting)
No signal input
✓
Run/stop signal input
External switch signal input (N.O. type)
External switch signal input (N.C. type)
Remote signal input
∗
1
∗
1
:
When the serial communication protocol is set to “Simplified communication protocol 2”, it is
not possible to set to “Remote signal”.
Setting/Checking: Contact input signal 2 type
39.
Press the [SEL] key once.
Setting screen of contact input signal 2 type
is displayed on the digital display.
PV
SV
40.
Select contact input signal 2 type with [
▲
] key or [
▼
] key, and press [SEL] key to enter.
Table 5.21-21 Setting of the contact input signal 2 type
Set value
Explanation
Initial value
(Default setting)
Setting/checking are not available when
contact input signal 2 setting is OFF.
Alternate signal
✓
Momentary signal
∗
1
∗
1: This can be set only when the contact input signal 2 is set to "Run/Stop signal input" or "Remote
signal".
Setting/Checking: Contact input signal 2 delay timer of reading
41.
Press the [SEL] key once.
Setting screen of contact input signal 2 delay timer
is displayed on the digital display.
PV
SV
Summary of Contents for HRS090-A
Page 8: ...HRX OM S004 Contents HRS Series...
Page 20: ...HRX OM S004 Chapter 2 Name and Function of Parts 2 4 Operation display panel HRS Series 2 6...
Page 56: ...HRX OM S004 Chapter 3 Transport and Setting Up 3 5 Circulating Fluid Supply HRS Series 3 36...
Page 164: ......
Page 174: ......
Page 192: ...HRX OM S004 Chapter 8 Documents 8 9 Daily Check Sheet HRS Series 8 18...
Page 195: ......