HPM6 Power Management Controller User Manual
Page 89 of
146
No.
Items
Range
Default
Description
205.
Alarm Self-lock
(0-1)
0: Disable
206.
Threshold
(0-200.0)%
20.0
207.
Return Value
(0-200.0)%
18.0
208.
Delay Value
(0.1-3600.0)s 60.0
209.
Alarm Type
(0-6)
1: Warning
210.
Active Range
(0-20)
3: After Gen
Close
211.
Reactive
Distribution
Imbalance 1
Action
(0-1)
1: Enable
Action for reactive distribution
percentage is greater that set
value.
212.
Auto ACK
(0-1)
0: Disable
213.
Alarm Self-lock
(0-1)
0: Disable
214.
Threshold
(0-200.0)%
20.0
215.
Return Value
(0-200.0)%
18.0
216.
Delay Value
(0.1-3600.0)s 60.0
217.
Alarm Type
(0-6)
1: Warning
218.
Active Range
(0-20)
3: After Gen
Close
219.
Reactive
Distribution
Imbalance 2
Action
(0-1)
0: Disable
220.
Auto ACK
(0-1)
0: Disable
221.
Alarm Self-lock
(0-1)
0: Disable
222.
Threshold
(0-200.0)%
20.0
223.
Return Value
(0-200.0)%
18.0
224.
Delay Value
(0.1-3600.0)s 60.0
225.
Alarm Type
(0-6)
1: Warning
226.
Active Range
(0-20)
3: After Gen
Close
227.
NEL 1
Trip
Auto ACK
(0-1)
0: Disable
228.
Alarm Self-lock
(0-1)
0: Disable
229.
Alarm Type
(0-6)
1: Warning
230.
Active Range
(0-20)
0: Always
Active
231.
Power Trip
Action
(0-1)
1: Enable
When any bus genset power is
greater than set value, external
non-essential load 1 will trip.
232.
Threshold (0-200.0)%
100.0
233.
Return
Value
(0-200.0)%
99.0
234.
Delay
Value
(0.1-3600.0)s 5.0
235.
Current
Trip
Action
(0-1)
0: Disable
When any bus genset current
is greater than set value,
external non-essential load 1
will trip.
236.
Threshold (0-200.0)%
100.0
237.
Return
Value
(0-200.0)%
99.0
238.
Delay
Value
(0.1-999.9)s
5.0