HPM6 Power Management Controller User Manual
Page 7 of
146
1.
OVERVIEW
HPM6 power management controller is a special power management system for marine
applications. The system carries out genset control, protection, power detection functions. The system
is a true multi-master system whose power management function is realized by calculating all
generator control units. One of the control units is internally defined as the “command unit”. This unit is
the one where start priority and other power management-related functions are calculated.
HPM6 can realize up to 20 gensets automatic synchronization and load sharing. Should the
command unit fail, the power management calculations will automatically be transferred to the next
available control unit. Each control unit is connected via network bus, which has device level ring
redundancy function.
2.
MODEL CONFIGURATION
According to the functions, it is divided into HPM6-DG diesel genset power management controller
and HPM6-SG genset power management controller. All controllers share one set of hardware (master
control display module).
3.
PERFORMANCE AND CHARACTERISTICS
HPM6 power management controller adopts split-type design, which is composed of display
module HPM6D and master control module HPM6M.
─
4.3-inch LCD, 480x272 resolution with backlight, Chinese, English and other languages display
interface;
─
Suitable for 3-phase 4-wire, 3-phase 3-wire, 2-phase 3-wire and single phase systems with
frequency 50/60Hz;
─
PLC function enables user to define control logic;
─
User-defined system SLD function;
─
3-level password protection, two password permissions can customize user configuration items,
i.e. configuration items that user can modify can be customized;
─
3 accumulated data, two user accumulated data (user A and user B), user can clear accumulated
data. 3 accumulated data are simultaneously and synchronously calculated, but user A and user B
data can be cleared at any time;
─
Parameter setting: parameters can be modified, most of them can be configured from front panel
of the controller and all of them can be configured using PC via USB, RS485 or RJ45 ports;
─
Alarm log, which cannot be lost even in case of power outage, maximum 500 pieces can be
recorded;
─
Event log, which cannot be lost even in case of power outage, maximum 500 pieces can be
recorded;
─
User-defined protocol content function;
─
User-defined bus data function, can read other genset controller data from one controller;
─
Harmonic analysis and generator voltage, current waveform display function;
─
Monitor data curve at real time;