HPM6 Power Management Controller User Manual
Page 87 of
146
No.
Items
Range
Default
Description
132.
Set
Auto ACK
(0-1)
0: Disable
value is greater than set value,
it will initiate alarm signal and
alarm information will be
displayed on LCD.
133.
Alarm Self-lock
(0-1)
0: Disable
134.
Threshold
(0-200.0)%
120.0
135.
Return Value
(0-200.0)%
119.0
136.
Delay Value
(0.1-3600.0)s 10.0
137.
Alarm Type
(0-6)
1: Warning
138.
Active Range
(0-20)
0: Always
Active
139.
Over Power 2
Set
Action
(0-1)
1: Enable
140.
Auto ACK
(0-1)
0: Disable
141.
Alarm Self-lock
(0-1)
0: Disable
142.
Threshold
(0-200.0)%
130.0
143.
Return Value
(0-200.0)%
129.0
144.
Delay Value
(0.1-3600.0)s 5.0
145.
Alarm Type
(0-6)
2: Trip
146.
Active Range
(0-20)
0: Always
Active
147.
Reverse
Power 1 Set
Action
(0-1)
1: Enable
When
controller
detects
reverse power value is greater
than set value, it will initiate
alarm
signal
and
alarm
information will be displayed
on LCD.
148.
Auto ACK
(0-1)
0: Disable
149.
Alarm Self-lock
(0-1)
0: Disable
150.
Threshold
(0-200.0)%
8.0
151.
Return Value
(0-200.0)%
7.0
152.
Delay Value
(0.1-3600.0)s 5.0
153.
Alarm Type
(0-6)
1: Warning
154.
Active Range
(0-20)
0: Always
Active
155.
Reverse
Power 2 Set
Action
(0-1)
1: Enable
156.
Auto ACK
(0-1)
0: Disable
157.
Alarm Self-lock
(0-1)
0: Disable
158.
Threshold
(0-200.0)%
15.0
159.
Return Value
(0-200.0)%
14.0
160.
Delay Value
(0.1-3600.0)s 2.0
161.
Alarm Type
(0-6)
2: Trip
162.
Active Range
(0-20)
0: Always
Active
163.
Low Power
Factor 1
Alarm Set
Action
(0-1)
1: Enable
When controller detects power
factor is lower than set value, it
will initiate alarm signal and
alarm information will be
displayed on LCD.
164.
Auto ACK
(0-1)
0: Disable
165.
Alarm Self-lock
(0-1)
0: Disable
166.
Threshold
(0-200.0)%
0.70
167.
Return Value
(0-200.0)%
0.75
168.
Delay Value
(0.1-3600.0)s 5.0
169.
Alarm Type
(0-6)
1: Warning