![Smartgen HPM6 User Manual Download Page 79](http://html1.mh-extra.com/html/smartgen/hpm6/hpm6_user-manual_1297544079.webp)
HPM6 Power Management Controller User Manual
Page 79 of
146
No.
Items
Range
Default
Description
130
Active
Range
(0-20)
3: After Gen
Close
131
Voltage
Imbalance
2 Set
Action
(0-1)
0: Disable
132
Auto ACK
(0-1)
0: Disable
133
Alarm
Self-lock
(0-1)
0: Disable
134
Threshold (0-200.0)%
10.0
135
Set Value
(0-200.0)%
5.0
136
Delay
(0.1-3600.0)s
5.0
137
Alarm Type (0-6)
1: Warning
138
Active
Range
(0-20)
3: After Gen
Close
139
Over
Frequency
1 Set
Action
(0-1)
1: Enable
Setting value is percentage of
generator rated frequency. Delay
value and return value can be set
according to actual situation.
140
Auto ACK
(0-1)
0: Disable
141
Alarm
Self-lock
(0-1)
0: Disable
142
Threshold (0-200.0)%
105.0
143
Return
Value
(0-200.0)%
104.0
144
Delay Value (0.1-3600.0)s
5.0
145
Alarm Type (0-6)
1: Warning
146
Active
Range
(0-20)
0:
Always
Active
147
Over
Frequency
2 Set
Action
(0-1)
1: Enable
148
Auto ACK
(0-1)
0: Disable
149
Alarm
Self-lock
(0-1)
0: Disable
150
Threshold (0-200.0)%
107.0
151
Return
Value
(0-200.0)%
106.0
152
Delay Value (0.1-3600.0)s
3.0
153
Alarm Type (0-6)
2: Trip
154
Active
Range
(0-20)
0:
Always
Active
155
Over
Frequency
3 Set
Action
(0-1)
0: Disable
156
Auto ACK
(0-1)
0: Disable
157
Alarm
Self-lock
(0-1)
0: Disable
158
Threshold (0-200.0)%
110.0
159
Return
Value
(0-200.0)%
109.0
160
Delay Value (0.1-3600.0)s
1.0