Illustration for the fixed heavy consumer sequence diagram:
a)
The HC1 request power is 300kW, HC1 rated power is 150kW;
b)
The bus reserves 300kW for HC1;
c)
The bus has enough redundant power and starts after heavy consumer stability delay;
d)
After the heavy consumer stability delay, the controller starts to output HC response signal;
e)
During or after the output delay of heavy consumer response, the bus has different processing
states for HC1 heavy consumer according to the different states of heavy consumer feedback and
request signals;
f)
If the heavy consumer feedback is active, the bus will no longer reserve any power for HC1;
g)
If the heavy consumer feedback is inactive, the bus will only reserve the rated power for HC1 when
heavy consumer request is active;
h)
If the heavy consumer feedback is inactive, the bus will not reserve any power for HC1 when heavy
consumer request is inactive.
Analog feedback is shown in the figure below:
Fig.18 – Analog Heavy Consumer Sequence Diagram 1