HPM6 Power Management Controller User Manual
Page 126 of
146
No.
Item
Range
Default
Description
Max.
Analog Output Port 3
15
Function
(0-4)
0
0: Not used
1: GOV
2: AVR
3: Transmitter
16
Output Type
(0-0)
0
0: Current
17
Transmitter
Config.
Config (0-20)
0
Refer to
18
OUT
Min.
(-20.0-20.0)mA 4
Transmitter configuration min value
corresponds to output min value, max
value corresponds to output max
value.
19
OUT
Max.
(-20.0-20.0)mA 20
20
Config
Min.
(-1000-32000)
0
21
Config
Max.
(-1000-32000)
500
Analog Output Port 4
22
Function
(0-4)
0
0: Not used
1: GOV
2: AVR
3: Transmitter
23
Output Type
(0-0)
0
0: Current
24
Transmitter
Config.
Config (0-20)
0
Refer to
25
OUT
Min.
(-20.0-20.0)mA 4
Transmitter configuration min value
corresponds to output min value, max
value corresponds to output max
value.
26
OUT
Max.
(-20.0-20.0)mA 20
27
Config
Min.
(-1000-32000)
0
28
Config
Max.
(-1000-32000)
500
Table 39 – Transmitter Configuration Functions
No.
Name
Description
0
Not Used
Transmitter function is not used.
1
Bus Voltage
2
Bus Frequency
3
Bus Active Power
4
Bus Reactive Power
5
Bus Apparent Power