HPM6 Power Management Controller User Manual
Page 134 of
146
No.
Item
Range
Default
Description
50
Fixed Power Factor
(0-100.0)%
8.0
The genset power factor in fixed
power mode.
Fixed Active Power
51
Output Min. Value
(0-100)%
5
When the active load percentage of
any one on-grid genset is lower
than set min. value and continues
min delay time, fixed power genset
outputs in active power.
52
Output Min. Value Delay
(0-3600.0)s
0.5
53
Output Max. Value
(0-100)%
95
When the active load percentage of
any one on-grid genset is greater
than set max. value and continues
max delay time, fixed power genset
outputs in active power.
54
Output Max. Value Delay
(0-3600.0)s
0.5
Fixed Reactive Power
55
Output Min. Value
(0-100)%
5
When the reactive load percentage
of any one on-grid genset is lower
than set min. value and continues
min delay time, fixed power genset
outputs in reactive power.
56
Output Min. Value Delay
(0-3600.0)s
0.5
57
Output Max. Value
(0-100)%
95
When the reactive load percentage
of any one on-grid genset is greater
than set max. value and continues
max delay time, fixed power genset
outputs in reactive power.
58
Output Max. Value Delay
(0-3600.0)s
0.5
SG Fixed Power Mode
59
DG Min. On-load%
(0-100.0)%
0.0
When the controller works in both
SG mode and fixed power mode, if
the total load is lower than the
active power of SG fixed output, DG
takes the set value and the
remaining power is carried by SG.
If this value is 0, when the total
power is lower than the fixed active
power output of SG, DG does not
start with load.
60
SG Max. On-load%
(0-100.0)%
100.0
When the controller works in both
SG mode and fixed power mode, if
the total load is greater than the SG
and DG fixed active power
percentage, DG will be loaded to
the fixed active power percentage,
the remaining power will be loaded