83
Delay Value (0.1-3600.0)s
8.0
84
Alarm Type (0-6)
2: Trip
85
Active
Range
(0-20)
0: Always
Active
86
Over
Frequency 3
Set
Action
(0-1)
0: Disable
87
Auto ACK
(0-1)
0: Disable
88
Alarm
Self-lock
(0-1)
0: Disable
89
Threshold
(0-200.0)%
120.0
90
Return
Value
(0-200.0)%
119.0
91
Delay Value (0.1-3600.0)s
6.0
92
Alarm Type (0-6)
2: Trip
93
Active
Range
(0-20)
0: Always
Active
94
Under
Frequency 1
Set
Action
(0-1)
1: Enable
95
Auto ACK
(0-1)
0: Disable
96
Alarm
Self-lock
(0-1)
0: Disable
97
Threshold
(0-200.0)%
96.0
98
Return
Value
(0-200.0)%
97.0
99
Delay Value (0.1-3600.0)s
5.0
100
Alarm Type (0-6)
1: Warning
101
Active
Range
(0-20)
4: Gen
Close on
Bus
102
Under
Frequency 2
Set
Action
(0-1)
1: Enable
103
Auto ACK
(0-1)
0: Disable
104
Alarm
Self-lock
(0-1)
0: Disable
105
Threshold
(0-200.0)%
93.0
106
Return
Value
(0-200.0)%
94.0
107
Delay Value (0.1-3600.0)s
10.0
108
Alarm Type (0-6)
2: Trip
109
Active
Range
(0-20)
4: Gen
Close on
Bus
110
Under
Frequency 3
Action
(0-1)
0: Disable
111
Auto ACK
(0-1)
0: Disable