HPM6 Power Management Controller User Manual
Page 94 of
146
No.
Items
Range
Default
Description
309.
Inquiry Signal
(0-1)
0
0 Continuous Signal; 1 Trigger
Signal
310.
ID
(0-128)
128
Heavy consumer ID number.
311.
Priority
(0-128)
128
HC priority. The smaller the
number, the higher the priority.
If the priority is same, HC with
small ID number, the priority is
high.
312.
Rated Power
(0-60000)kW 60
HC rated power.
313.
Inquiry Power
(0-60000)kW 90
The percentage of rated power
relative to heavy consumer.
314.
Stable Time
(0-3600)s
5
Bus stable time before HC
running.
315.
ACK Time
(0-3600)s
5
Output ACK signal time after
meeting HC demand. It is
continuous output when set as
0.
316.
Feedback Failure
Time
(0-3600)s
5
Feedback signal detection
time after HC ACK. It doesn’t
detect feedback failure when
set as 0.
317.
Request Failure
Time
(0-3600)s
120
Time between receiving HC
inquiry signal and HC ACK.
Controller will initiate alarm
signal when time is over. It
doesn’t detect request failure
when set as 0.
318.
Request Failure
Action
(0-2)
0
0 Alarm
1 Trip NEL
2 Alarm and Trip NEL
319.
Chinese
Character String
HC4
Character string only can be
set via upper computer.
320.
English Character
String
HC4