HPM6 Power Management Controller User Manual
Page 103 of
146
No.
Name
Description
Auto
Mode
Semi-auto
Mode
Manual
Mode
is active.
7.
Volt Drop
Voltage drop relay is active when the input
is active.
Х
Х
√
8.
HC 1 Inquiry
Heavy consumer 1 inquiry.
Acknowledge signal is initiated if the
requirements are satisfied. If not satisfied,
standby gensets will be started to meet
with the requirement.
√
√
Х
9.
HC 1 Feedback
After breaker closing, feedback signal is
sent to controller to ensure the HC1 has
loaded.
√
√
Х
10.
HC 2 Inquiry
Heavy consumer 2 inquiry.
Acknowledge signal is initiated if the
requirements are satisfied. If not satisfied,
standby gensets will be started to meet
with the requirement.
√
√
Х
11.
HC 2 Feedback
After breaker closing, feedback signal is
sent to controller to ensure the HC2 has
loaded.
√
√
Х
12.
HC 3 Inquiry
Heavy consumer 3 inquiry.
Acknowledge signal is initiated if the
requirements are satisfied. If not satisfied,
standby gensets will be started to meet
with the requirement.
√
√
Х
13.
HC 3 Feedback
After breaker closing, feedback signal is
sent to controller to ensure the HC3 has
loaded.
√
√
Х
14.
HC 4 Inquiry
Heavy consumer 4 inquiry.
Acknowledge signal is initiated if the
requirements are satisfied. If not satisfied,
standby gensets will be started to meet
with the requirement.
√
√
Х
15.
HC 4 Feedback
After breaker closing, feedback signal is
sent to controller to ensure the HC4 has
loaded.
√
√
Х
16.
Engine Fault
Engine fault feedback input.
√
√
Х
17.
Alarm Inhibit
All alarms are inhibited after input is active.
√
√
√
18.
Alarm Mute
Mute the panel buzzer and audible alarm
not output.
√
√
√
19.
Alarm Reset
Reset alarms.
√
√
√
20.
Alarm ACK
Acknowledge all alarms.
√
√
√