![Smartgen HPM6 User Manual Download Page 69](http://html1.mh-extra.com/html/smartgen/hpm6/hpm6_user-manual_1297544069.webp)
HPM6 Power Management Controller User Manual
Page 69 of
146
No.
Items
Range
Default
Description
1: Enable
delay value can be set.
23
Auto ACK
(0-1)
0: Disable
1: Enable
0: Disable
24
Alarm
Self-lock
(0-1)
0: Disable
1: Enable
0: Disable
25
Threshold
(0-200.0)%
110.0
26
Return
Value
(0-200.0)%
109.0
27
Delay Value (0.1-3600.0)s
5.0
28
Alarm Type
(0-6)
0: Block
1: Warning
2: Trip
3: Trip and Stop
4: Safety Trip
5: Safety Trip
and Stop
6: Indication
1: Warning
29
Active
Range
(0-20)
0: Always Active
1: Inactive
2: Before Gen
Close
3:
After
Gen
Close
4: Gen Close on
Bus
5: No Gen Close
on Bus
6: Gen Normal
7: Other Gens
Close
8: Start Delay
9:
After
Gen
Close Delay
10: Before Gen
Close Delay
11: Gen Load
Normal
12: Gen Close
0: Always
Active