HPM6 Power Management Controller User Manual
Page 76 of
146
No.
Items
Range
Default
Description
Range
Normal
67
Voltage
SHD 2 Set
Action
(0-1)
0: Disable
68
Auto ACK
(0-1)
0: Disable
69
Alarm
Self-lock
(0-1)
0: Disable
70
Threshold (0-200.0)%
10.0
71
Return
Value
(0-200.0)%
5.0
72
Delay Value (0.1-3600.0)s
5.0
73
Alarm Type (0-6)
1: Warning
74
Active
Range
(0-20)
6:
Gen
Normal
75
Over
Voltage 1
Set
Action
(0-1)
0: Disable
1: Enable
1: Enable
Setting value is percentage of
generator rated voltage. Delay value
and return value can be set.
76
Auto ACK
(0-1)
0: Disable
1: Enable
0: Disable
77
Alarm
Self-lock
(0-1)
0: Disable
1: Enable
0: Disable
78
Threshold (0-200.0)%
105.0
79
Return
Value
(0-200.0)%
104.0
80
Delay Value (0.1-3600.0)s
5.0
81
Alarm Type
(0-6)
0: Block
1: Warning
2: Trip
3: Trip and Stop
4: Safety Trip
5: Safety Trip and
Stop
6: Indication
1: Warning
82
Active
Range
(0-20)
0: Always Active
1: Inactive
2:
Before
Gen
Close
3: After Gen Close
4: Gen Close on
Bus
0: Always
Active