HPM6 Power Management Controller User Manual
Page 34 of
146
No.
Types
Description
Alarm Type
14
Earth Fault 2
Disabled
15
External
Overcurrent
Short
Alarm when external overcurrent input port is
active.
Trip
Always
active.
Power Protection
1
Reverse Power
1
When controller detects the reverse power value
(power is negative) has fallen below than the set
value 1, it will initiate a trip alarm.
Warn
Always
active.
2
Reverse Power
2
When controller detects the reverse power value
(power is negative) has fallen below than the set
value 2, it will initiate a trip alarm.
Trip
Always
active.
3
Over Power 1
When controller detects the power value (power is
positive) has exceeded the set value 1, it will
initiate a warning alarm.
Warn
Always
active.
4
Over Power 2
When controller detects the power value (power is
positive) has exceeded the set value 2, it will
initiate a trip alarm.
Trip
Always
active.
5
Non Essential
Load 1 Trip
When controller detects the power value (power is
positive) has exceeded the
Non Essential Load 1
Trip
set value, it will trip and initiate alarm.
Warn
(Non Essential
Load 1 Trip)
It is active after the Non
Essential Load switch 1
has closed.
6
Non Essential
Load 2 Trip
When controller detects the power value (power is
positive) has exceeded the
Non Essential Load 2
Trip
set value, it will trip and initiate alarm.
Warn
(Non Essential
Load 2 Trip)
It is active after the Non
Essential Load switch 2
has closed.
7
Non Essential
Load 3 Trip
When controller detects the power value (power is
positive) has exceeded the
Non Essential Load 3
Trip
set value, it will trip and initiate alarm.
Warn
(Non Essential
Load 3 Trip)
It is active after the Non
Essential Load switch 3
has closed.
8
Gen Insufficient
Capacity
When controller detects all normal gensets are on
grid and the remaining power cannot request
power, it will initiate a warning alarm.
Warn
Always active.
9
Unbalanced
Distribution of
Active Power 1
When the controller detects the unbalanced
distribution of active power percentage is greater
than the set value, the unbalanced active power
distribution outputs and alarms.
Warn
It is active after gen has
closed.
10
Unbalanced
Distribution of
Active Power 2
Disabled