HPM6 Power Management Controller User Manual
Page 73 of
146
No.
Items
Range
Default
Description
112
Set
Alarm
Self-lock
(0-1)
0: Disable
113
Threshold
(0-200.0)%
92.0
114
Set Value
(0-200.0)%
93.0
115
Delay
(0.1-3600.0)s
8.0
116
Alarm Type (0-6)
2: Trip
117
Active
Range
(0-20)
4: Gen
Close on
Bus
12.3
GENERATOR SETTING
Table 29 – Generator Parameter Settings
No.
Items
Range
Default
Description
Generator Setting
1
AC System
(0-3)
0: 3P3W
0: 3 phase, 4 wire (3P4W);
1: 3 phase, 3 wire (3P3W);
2: 2 phase, 3 wire (2P3W);
3: Single phase, 2 wire (1P2W).
2
Rated Voltage
(30-30000)V
400
To offer standards for detecting of
generator’s over/under voltage. (It is
primary voltage when using voltage
transformer; it is line voltage when
AC system is 3P3W while it is phase
voltage when using other AC
system).
3
Min. Loading Voltage
(0-200.0)%
95.0
Setting value is percentage of
generator rated voltage. Detect
when controller prepares loading.
When generator voltage is between
min loading voltage and max
loading voltage, it will enter into
normally running.
4
Max. Loading Voltage
(0-200.0)%
105.0
5
Crank Disconnect Volt
(0-200.0)%
80.0
To offer standards for detecting
crank disconnect voltage is satisfied
or not.
6
Rated Frequency
(10.0-75.0)Hz
50.0
To offer standards for detecting
over/under/load frequency.
7
Min. Loading Frequency (0-200.0)%
94.0
Setting value is percentage of
generator rated frequency. Detect
when controller prepares loading.
When generator frequency
is
between min loading frequency and
8
Max. Loading Frequency (0-200.0)%
101.0