HPM6 Power Management Controller User Manual
Page 37 of
146
No.
Types
Description
Alarm Type
13
Bustie Series
Switch 1 Fault
controller detects bustie series switch fault signal
(signal is inconsistent), it will initiate an alarm.
Disabled
14
Bustie Series
Switch 2 Fault
Disabled
15
Bustie Series
Switch 3 Fault
Disabled
16
Bustie Series
Switch 4 Fault
Disabled
17
Bustie Series
Switch 5 Fault
Disabled
18
Shore Switch 1
Fault
When controller detects shore switch fault signal
(signal is inconsistent), it will initiate an alarm.
Warn
Always active.
19
Shore Switch 2
Fault
Disabled
20
Shore Switch 3
Fault
Disabled
21
Shore Switch 4
Fault
Disabled
22
Shore Switch 5
Fault
Disabled
23
Abnormal Trip
of Main Switch
When controller detects the input is active, it will
initiate a trip alarm.
Trip
It is active after gen has
closed.
24
External Open
of Main Switch
When controller is grid-connected with load in
non-manual mode, gen close input port is inactive
and power and current are both 0, it will initiate a
trip alarm.
Trip
It is active after gen has
closed.
25
Bus Break Fault
When bus break function is enabled, if other
controllers on the bus have bus break input, and
current bus break input port is inactive, it will
initiate a warning alarm.
Warn
It is active after bus
break is enabled.
26
SG Solenoid
Valve Fault
When SG mode is enabled and SG solenoid valve
closed input is configured, if SG valve close status
and controller valve close/open status are
inconsistent, it will initiate a warning alarm.
Warn
It is active after SG
mode is enabled and SG
solenoid valve close
input is configured.
27
Volt
Asynchrony
When voltage asynchrony is detected after
synchronous close, controller will initiate a trip
alarm.
Trip
It is active after gen has
closed.