HPM6 Power Management Controller User Manual
Page 64 of
146
12.
PARAMETER SETTINGS
This part contains all controller parameters, in which partial parameters only can be configured by
upper computer.
12.1
MODULE SETTING
Table 27 – Module Parameter Settings
No.
Item
Range
Default
Description
Module Setting
1
Controller Type
(0-1)
0
0: DG Mode
1: SG Mode
2
Power On Mode
(0-2)
0
0: Semi-auto Mode; 1: Auto Mode; 2:
Manual Mode.
3
Language
(0-2)
0
0: Simplified Chinese; 1: English; 2:
Others.
4
Password
(0-65535)
00318
It is used for entering parameter
setting.
5
Engine Fault Action
(0-5)
0: Block
Alarm action type when engine fault
input port is active.
6
SG Mode
(0-2)
0
0: Load Takeover Mode
1: Fixed Power Mode
2: Load Sharing Mode
7
Self-check Abnormal
Action
(0-2)
1: Force to
Manual Mode
If controller self-check is abnormal,
corresponding actions will be
initiated.
0: No Action
1: Force to Manual Mode
2: Force to Semi-auto Mode
8
Safe Alarm Action
(0-1)
0: Disable
If it is enabled, in semi-auto mode,
safety trip and safety trip and stop
alarms will execute corresponding
actions.
If it is disabled, in semi-auto mode,
there are only safety trip and safety
trip and stop alarms without action.
9
Safe Mode with Load (0-1)
1: Enable
Load or not after genset starts in
safe mode.
10
Start Enable during
Stopping
(0-1)
0
0: Disabled
11
USB Enable
(0-1)
0
0: Disabled
12
USB Data Record
Interval
(0.1-3600.0)s
1.0
Interval time of USB data record in
genset running.
13
Alarm Data Analysis (0.0-60.0)s
0.1
Interval time of alarm data analysis