HPM6 Power Management Controller User Manual
Page 15 of
146
6.
OPERATION
6.1
PANEL DISPLAY
HPM6D display module TFT LCD is 4.3 inches with 480x272 resolutions, as follows:
Fig.1 – HPM6 Display Panel
Table 4 – Alarm Indicator Introduction
Alarm Type
Indicator Color
Indicator Status
Indication Alarm
Green
Slowly flash (once per second)
Warning Alarm
Yellow
Slowly flash (once per second)
Block Alarm
Yellow
Slowly flash (once per second)
Safety Trip Alarm
Red
Fast flash (twice per second)
Safety Trip and Stop Alarm
Red
Fast flash (twice per second)
Trip Alarm
Red
Fast flash (twice per second)
Trip and Stop Alarm
Red
Fast flash (twice per second)
NOTE1:
Alarm Indicator (red, green, yellow): flashes when alarm is not acknowledged, always illuminates when alarm is
acknowledged but not disappear, extinguishes when the alarm is disappeared;
NOTE2:
Power Indicator (green): green light always illuminates when the power is normal;
NOTE3:
Running Indicator (red and green, yellow represents green and red lights are illuminated simultaneously):
Green light always illuminates: genset is normally running;
Red light always illuminates: ready to start signal abnormal or genset in start inhibit status;
Yellow light always illuminates: genset normal running, but standby engine starts signal abnormal or genset in
start inhibit status;
Light off: genset standby and normal running;
NOTE4:
Self-check Indicator (green): green light illuminates when self-check is normal;
NOTE5:
Gen Normal Indicator (green): it always illuminates when generating is normal, flashes when generating is
abnormal, extinguishes when there is no generating;
NOTE6:
Bus Normal Indicator (green): it always illuminates when bus is normal, extinguishes when bus is abnormal or
bus voltage blackout;
NOTE7:
Top Priority Indicator (green): When the top priority is enabled, press current controller “Top Priority Key”, system
will sort all gensets priority and set the current genset as the first (priority value is smallest), controller indicator always
illuminates (on-grid genset in non-auto mode is prior to genset in auto mode), otherwise it will extinguish. When the top
priority is disabled, press current controller “Top Priority Key”, indicator illuminates, representing current genset is master,