HPM6 Power Management Controller User Manual
Page 97 of
146
No.
Items
Range
Default
Description
13
Delay Value
(0.1-3600.0)s
5.0
14
Alarm Type
(0-6)
1
15
Active
Range
(0-20)
0: Always
Active
16
Upper
Limit 2
Action
(0-1)
0: Disable
17
Auto ACK
(0-1)
0: Disable
18
Alarm
Self-lock
(0-1)
0: Disable
19
Threshold
(0.0-1000.0)°C
90.0
20
Return Value (0.0-1000.0)°C
80.0
21
Delay Value
(0.1-3600.0)s
5.0
22
Alarm Type
(0-6)
1
23
Active
Range
(0-20)
0: Always
Active
24
Lower
Limit 1
Action
(0-1)
0: Disable
25
Auto ACK
(0-1)
0: Disable
26
Alarm
Self-lock
(0-1)
0: Disable
27
Threshold
(0.0-1000.0)°C
10.0
28
Return Value (0.0-1000.0)°C
20.0
29
Delay Value
(0.1-3600.0)s
5.0
30
Alarm Type
(0-6)
1
31
Active
Range
(0-20)
0: Always
Active
32
Lower
Limit 2
Action
(0-1)
0: Disable
33
Auto ACK
(0-1)
0: Disable
34
Alarm
Self-lock
(0-1)
0: Disable
35
Threshold
(0.0-1000.0)°C
20.0
36
Return Value (0.0-1000.0)°C
30.0
37
Delay Value
(0.1-3600.0)s
5.0
38
Alarm Type
(0-6)
1
39
Active
Range
(0-20)
0: Always
Active
40
1
st
Point X (Resistance)
(0-6000)
0
User-defined curve.
41
2
nd
Point X (Resistance)
(0-6000)
21
42
3
rd
Point X (Resistance)
(0-6000)
28
43
4
th
Point X (Resistance)
(0-6000)
39
44
5
th
Point X (Resistance)
(0-6000)
56
45
6
th
Point X (Resistance)
(0-6000)
116
46
7
th
Point X (Resistance)
(0-6000)
258
47
8
th
Point X (Resistance)
(0-6000)
300