![Smartgen HPM6 User Manual Download Page 98](http://html1.mh-extra.com/html/smartgen/hpm6/hpm6_user-manual_1297544098.webp)
HPM6 Power Management Controller User Manual
Page 98 of
146
No.
Items
Range
Default
Description
48
1
st
Point Y (Value)
(0-10000)
140
49
2
nd
Point Y (Value)
(0-10000)
110
50
3
rd
Point Y (Value)
(0-10000)
100
51
4
th
Point Y (Value)
(0-10000)
90
52
5
th
Point Y (Value)
(0-10000)
80
53
6
th
Point Y (Value)
(0-10000)
60
54
7
th
Point Y (Value)
(0-10000)
40
55
8
th
Point Y (Value)
(0-10000)
20
Analog Input Port 2
56
Function
(0-4)
0
0: Not Used
1: Fixed Active Power Input
2: Fixed Reactive Power Input
3: HC Feedback Input
4: Temperature Sensor
57
Type
(0-2)
0
0: Resistance Type
1: Current Type
2: Voltage Type
58
Input Min. Value
(0.0-1000.0)Ω/mA/V 0.0
Unit is changed according to
type.
59
Input Max Value
(0.0-1000.0)Ω/mA/V 600.0
60
HC Feedback Range
(0-60000)kW
100
61
Open Action
(0-6)
1
62
Curve Type
(0-15)
0
63
Upper
Limit 1
Action
(0-1)
0: Disable
64
Auto ACK
(0-1)
0: Disable
65
Alarm
Self-lock
(0-1)
0: Disable
66
Threshold
(0.0-1000.0)°C
100.0
67
Return Value (0.0-1000.0)°C
90.0
68
Delay Value
(0.1-3600.0)s
5.0
69
Alarm Type
(0-6)
1
70
Active
Range
(0-20)
0: Always
Active
71
Upper
Limit 2
Action
(0-1)
0: Disable
72
Auto ACK
(0-1)
0: Disable
73
Alarm
Self-lock
(0-1)
0: Disable
74
Threshold
(0.0-1000.0)°C
90.0
75
Return Value (0.0-1000.0)°C
80.0
76
Delay Value
(0.1-3600.0)s
5.0
77
Alarm Type
(0-6)
1
78
Active
Range
(0-20)
0: Always
Active