![Smartgen HPM6 User Manual Download Page 42](http://html1.mh-extra.com/html/smartgen/hpm6/hpm6_user-manual_1297544042.webp)
HPM6 Power Management Controller User Manual
Page 42 of
146
10.3
HPM6M TERMINAL DESCRIPTION
Fig.5 – HPM6M Terminal Drawing
Terminal description: NO means normally open; NC means normally close.
10.3.1
TS #1 POWER AND RELAY OUTPUT PORT
Table 18 – TS #1 Power and Relay Output Port
Terminal
Function
Cable Size
Description
Remark
1
PE
2.5mm
2
Ground connection
2
B-
2.5mm
2
DC(8~35)V
Controller power input
3
B+
2.5mm
2
4
COM1
1.5mm
2
port 5~6 COM
5
DO1
1.5mm
2
Digital output port 1 (engine start) DC30V/8 A
6
DO2
1.5mm
2
Digital output port 2 (engine stop) DC30V/8 A
7
DO3
1.5mm
2
Digital output port 3 (speed raise) DC30V/8 A
8
DO4
1.5mm
2
Digital output port 3 (speed drop)
DC30V/8 A
9
DO5
1.5mm
2
Digital output port 5 (audible
alarm output)
DC30V/8 A
10
11
DO6_NO
1.5mm
2
Digital output port 6 (close
output)
DC30V/7 A
12
DO6 _COM
1.5mm
2
13
DO6 _NC
1.5mm
2
14
DO7 _NO
1.5mm
2
Digital output port 6 (open output) DC30V/7 A
15
DO7 _COM
1.5mm
2
16
DO7 _NC
1.5mm
2
NOTE:
If battery is used as power, power must directly connect the battery, but not starting power or charging
generator to ensure HPM6 stable supply.