HPM6 Power Management Controller User Manual
Page 104 of
146
No.
Name
Description
Auto
Mode
Semi-auto
Mode
Manual
Mode
21.
Alarm Unlock
Unlock all self-locked alarms.
√
√
√
22.
Lamp Test
Test all the LED lights.
√
√
√
23.
Light
Consumer
The controller doesn’t open breaker even if
the system load has fallen below the set
value.
√
√
Х
24.
Fixed Power IN
Fixed power output, when the “Fixed Power
Input” is active, the active power and the
reactive power can be adjusted via fixed
power setting parameter, or when the
external adjust input is active, the active
power and the reactive power can be
adjusted via external SPEED IN port and
VOLT IN port.
√
√
Х
25.
Manual Mode
Manual mode is carried out when the input
is active.
√
Х
Х
26.
Linear Start
Linear start mode is carried out when the
input is active.
√
Х
Х
27.
Duty Time Start
Duty time start mode is carried out when
the input is active.
√
Х
Х
28.
Auto Mode
Auto mode is carried out when the input is
active.
√
√
√
29.
Semi-auto
Mode
Semi-auto mode is carried out when the
input is active.
√
√
√
30.
Remote
Closing
Synchronous closing process will be
carried out when the input is active.
Х
√
Х
31.
Remote
Opening
Opening process will be carried out when
the input is active.
Х
√
Х
32.
Remote Start
The genset will start automatically when
the input is active.
Х
√
Х
33.
Remote Stop
The genset will stop after unload open
when the input is active.
Х
√
Х
34.
Safe Mode
An additional genset will be started even if
the power request is satisfied when the
input is active.
√
Х
Х
35.
Standby Engine
Connect the output signal when the
preparation work is done. If the function is
selected, the engine will be started when
the input is active.
√
√
Х
36.
Remote Mode
If it is configured, system is in remote
control status when the input is active,
remote control (start, close, open, stop)
Х
√
Х