HPM6 Power Management Controller User Manual
Page 108 of
146
No.
Name
Description
Auto
Mode
Semi-auto
Mode
Manual
Mode
Open Feedback
between bus 4 and bus 5.
82.
Bustie Switch 5
Open Feedback
Bustie switch open feedback input
between bus 5 and bus 6.
√
√
Х
83.
BTB0 Series
Switch Close
Feedback
It is close feedback input of series switch
of ring bustie switch. Series switch means
that if there are N buses, other series
switches besides bus contact switch
between bus 1 and bus N.
√
√
Х
84.
BTB1 Series
Switch Close
Feedback
Bustie series switch close feedback input
between bus 1 and bus 2.
√
√
Х
85.
BTB2 Series
Switch Close
Feedback
Bustie series switch close feedback input
between bus 2 and bus 3.
√
√
Х
86.
BTB3 Series
Switch Close
Feedback
Bustie series switch close feedback input
between bus 3 and bus 4.
√
√
Х
87.
BTB4 Series
Switch Close
Feedback
Bustie series switch close feedback input
between bus 4 and bus 5.
√
√
Х
88.
BTB5 Series
Switch Close
Feedback
Bustie series switch close feedback input
between bus 1 and bus 6.
√
√
Х
89.
Reserved
Power 1 Input
Power management system reserves
response set power for bus when the input
port is active.
√
Х
Х
90.
Reserved
Power 2 Input
√
Х
Х
91.
Reserved
Power 3 Input
√
Х
Х
92.
GB Storage
Feedback
It means genset mains switch energy
storage is finished, power management
system can initiate close operation when
the input port is active.
√
√
Х
93.
Single Pulse
Speed Raise
Input
In manual mode, when the input port is
closed once, the minimum pulse value is
output from speed control output port.
Х
Х
√
94.
Single Pulse
Speed Drop
Input
Х
Х
√
95.
Single Pulse
Voltage Raise
In manual mode, when the input port is
closed once, the minimum pulse value is
Х
Х
√