The settings have the following effect:
Entry Effect
Diagram
Autonomous The time switch only acts locally on the
RMS705B.
Slave
The time switch in RMS705B is not active.
The acting time switch is that one acting on
the geographical zone set on this controller
as the time switch receiving zone (time
switch slave (apartment)). The external time
switch must be set as the time switch
master.
31
23
Z0
8
Enter the "Geographical zone (apartment)" of the controller that is to receive the
time switch data during time switch operation "Slave".
If the time switch is operated as a "Slave", the output of the relevant time switch
assumes the following states:
Operating mode "Master time
switch" (RMx)
State of time switch output (RMS705B)
Comfort
On
Precomfort
Set in operating line "Transformation
Precomfort": On
or
Off
Economy
Off
State of time switch
output for slave operation
Main menu > Commissioning > Communication > Time switch > Time switch 1…6 >
Setting values
Operating line
Range
Factory setting
Time switch slave (apartment) ---,
1..126
---
Time switch operation*
Autonomous, Slave
Transformation Precomfort
Off, On
On
* Information line: Result of the setting.
7.1.2
Entries
You can select a specific 24-hour profile for the following days.
Main menu > Time switch 1…6 >
Set time switch
Operating line
Range
Factory setting
Monday to Sunday
On, Off
06:00
22:00
Special day
On, Off
06:00
22:00
You can enter for each day max. 6 entries in the 24-hour program.
Each entry must have the time of day and the required operating mode (On/Off).
You can copy data entered for a day to other days. If, for example, you entered
data for Monday, you can copy the same profile to all other working days (Monday
through Friday).
Copy 24-hour profiles