7
7-day time switch
7.1
Time switch
On / Off
Purpose
Six 7-day time switches with 6 switch-on
or
switch-off times are available for each
day.
Each time switch has operating line setting "Holiday priority".
If set to "Yes", the following occurs:
Features
The time switch is set to "Off" for the defined holidays.
Defined special days are activated.
The "Holiday priority" setting is ignored if the time switch is set to "Slave".
The output of the time switch can either be processed RMS-internal
or
output
directly via a relay output.
You can override the time switch output via operating switch
. It is visible on
the topmost user level.
Activate the time switches via operating line "Time switch".
Main menu > Commissioning > Extra configuration > Time switch > Time switch 1…6 >
Configuration
Operating line
Range
Factory setting
Time switch
Off, On
Off
Holiday priority
Yes, No
No
[Time switch 1] relay...
[Time switch 6] relay
---, N.Q1, N.Q2, ...
---
[Time switch 1] op selector....
[Time switch 6] op selector
Yes, No
No
7.1.1
Communication
The 7-day time switches of the RMS705B can run autonomously.
7-day time switch programs of the RMS705B can be received by other RMx
controllers if RMS705B is connected to other controllers via bus. In that case,
configure RMS705B as slave.
Summary:
Autonomous 7-day time switch.
7-day time switch from bus: 7-day time switch slave (receives time switch from
bus).
The status of 7-day time switches can be received only, but not sent to the bus.
Note
60 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
7-day time switch
01.04.2010