5.2.7
Multiple use of sensors
Function "Multiple use of sensors" allows for wiring a passive signal at an input
terminal directly to a Y-output and provide it as a DC 0…10 V signal. The signal
can then be fed to other devices.
Problem and solution
Ally passive temperature signal types (LG-Ni1000, 2x LG-Ni1000, T1, Pt1000) can
be converted and used multiple times.
Note
Main menu > Commissioning > Extra configuration > Sensor multiple use >
Configuration
Operating line
Adjustable values / Comment
Signal Y N.X1… Signal
Y RMZ787 (2).X4
N1.Y1…A8(2).Y2 /
Activate function by assigning an input terminal to the
output terminal.
When converting a passive signal to an DC 0...10 V signal, the preset allocation of
passive signal and temperature range can be adapted as needed. Do this via
parameters "Value low" and "Value high" (see Section 5.2.2).
Setting option
5.3
Digital inputs
Control function signals can be connected to the digital inputs.
Activate the digital inputs as described in Section 5.1.
5.3.1
Normal position
You can define the "Normal" position for each digital input.
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Inputs > ...X...
Setting values
Operating line
Range
Factory setting
Normal position
Open, Closed
Open
35 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Inputs
01.04.2010