Relative general limitation
One setpoint each for maximum ("Differential high") and minimum "Differential low"
differential temperature limitation can be entered.
The maximum and minimum differential temperature limitation can only be
enabled if the main controlled variable and the general limiter are configured
with the same unit (e.g. °C).
Notes
The set limitation setpoints relate to the differential (e.g. temperature) between
the main controlled variable and the general limiter.
1,
5 m
[General limit controller]
(f. e. supply air temperature)
Principle of operation
(example)
11.4.3 Troubleshooting
A check is made to see if a sensor is connected to the input when exiting the
commissioning menu.
If the sensor is connected but missing later, a fault message "[…] Sensor error
X.." is generated.
If there is no limitation sensor, limitation is disabled.
174 / 216