
9.2.3
Assign texts
You can assign a text to the enthalpy calculator block.
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Signal converter > Enthalpy calculator >
Operating line
Range
Factory setting
Enthalpy calculator
Max. 20 characters
Setting values
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to reset them.
9.2.4
Function check / wiring test
The inputs and outputs of the enthalpy calculator are displayed on the operator
unit.
Main menu > Signal converter > Enthalpy calculator >
Display values
Operating line
Comment
Enthalpy A
---, kJ/kg
Absolute humidity A
---, g/kg
Dew point
---, °C
Wet bulb temperature
---, °C
Enthalpy B
---, kJ/kg
Absolute humidity B
---, g/kg
Enthalpy difference
---, kJ/kg
Temperature input A
---, °C
Relative humidity input A
---, %
Temperature input B
---, °C
Relative humidity input B
---,%
You can directly control the enthalpy calculator during the wiring test.
Main menu > Commissioning > Wiring test > Outputs >
Wiring test
Operating line
Comment
Enthalpy A
---, 0...100 %
Absolute humidity A
---, 0...100 %
Dew point
---, 0...100 %
Wet bulb temperature
---, 0...100 %
Enthalpy B
---, 0...100 %
Absolute humidity B
---, 0...100 %
Enthalpy difference
---, 0...100 %
133 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies Signal
converter
01.04.2010