3.2
Basic configuration
Use the "Basic configuration" menu for the following settings:
Select basic type (only basic type S is available).
Assign extension modules to the controller position.
Internal configurations are deleted if you decide to later reset RMS705B to basic
type S.
Note
Main menu > Commissioning > Basic configuration >
Configuration
Operating line
Adjustable values / remarks
Basic type
S
Position 1
---, RMZ785, RMZ787(1), RMZ788(1)
Position 2
---, RMZ785, RMZ787(1), RMZ787(2), RMZ788(1), RMZ788(2)
Position 3
---, RMZ785, RMZ787(1), RMZ787(2), RMZ788(1), RMZ788(2)
Position 4
---, RMZ785, RMZ787(1), RMZ787(2), RMZ788(1), RMZ788(2)
3.2.1
Assign extension modules
You can extend RMS705B by appending extension modules.
Max. 4 extension modules can be connected to each RMS705B. Select from:
1x RMZ785:
Universal module with 8 universal inputs.
2x RMZ787:
Universal module with 4 universal inputs, 4 relay outputs.
2x RMZ788:
Universal module with 4 universal inputs, 2 modulating
outputs, 2 relay outputs
The extension modules are activated when physically plugged in and configured in
terms of software (type, position).
Position 1
Position 2
Position 3
Position 4
Example
RMS705B
RMZ785
RMZ787 (1)
RMZ787 (2)
RMZ788 (1)
Disconnect the system from power prior to attaching an extension module.
19 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Commissioning
01.04.2010