8.4.14 Motor kick
To prevent the motors (pumps) from seizing during longer off periods (e.g. heating
group in summer), a periodic motor kick can be enabled for each motor block.
When motor kick is active, the motors are switched on for 30 seconds once a
week regardless of any other functions and settings.
The motor kick is enabled by setting "Motor kick" to "Yes". If the setting is "No",
there is no motor kick.
In addition, a "Kick day" and "Kick time" can be set.
With the motor kick, the precommand output with its settable times is enabled
prior to the actual motor start. All other delay times are inactive.
The first speed is switched on for 2-speed motor operation, and both motors are
switched on alternating for twin motor operation.
Main menu > Commissioning > Settings > ....
or
Setting values
Main menu > Settings > Aggregates > Motor > Motor 1...6 >
Operating line
Range
Factory setting
Motor kick
Yes, No
No
Kick day
Mo, Tu, We, Th, Fr, Sa, Su
Mo
Kick time
00:00...23:59 h. m
10:00 h.m
8.4.15 Display values
The current state of the motors is displayed on the operator unit.
Main menu > Aggregates > Motor > Motor 1...6 >
Display values
1
or
2-speed motor
Operating line
Comment
[Motor 1]
precommand…
[Motor 6] precommand
Off, On.
Motor 1…6
Display of current motor speed:
Off, On
or
Off, Speed 1, Speed 2
Main menu > Aggregates > Motor > Motor 1...6 >
Display values
twin motor
Operating line
Comment
[Motor 1]
precommand…
[Motor 6] precommand
Off, On.
[Motor 1] A…
[Motor 6] A
Display of current motor speed:
Off, On.
[Motor 1] B…
[Motor 6] B
Display of current motor speed:
Off, On.