5.4
Pulse
An input with this identifier can be used to connect a pulse counter. Pulses with the
following specification can be received:
Mechanical sources (Reed contact) without Namur circuitry, max. pulse
frequency of 25 Hz and a min. 20 ms pulse duration.
Electronic pulse source with max. pulse frequency of 100 Hz and min. 5 ms
pulse duration.
5.4.1
Activate function
Main menu > Commissioning > Extra configuration > Input identifier >
Configuration
Operating line
Adjustable values / Comment
…X… Pulse
Electronic pulse sources (e.g. Open Collector outputs) generate shorter, less
bouncing pulses than mechanical pulse sources (e.g. relays or Reed contacts).
The type is adjustable.
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Inputs > ...X...
Setting value
Operating line
Range
Factory setting
Type Mechanically
or
Electronically
Mechanically
5.4.2
Connection diagram
G
G
G0
X...
M
G0
R1
N
31
23
A
10
AC
2
4
V
+/-
+/-
R1
Reed pulse source.
37 / 216
Siemens
Switching and monitoring device RMS705B
CE1P3124en
Building Technologies
Inputs
01.04.2010